| Troubleshooting
       Dehydrator fails to start: 
 Check the power cord to be sure power is reaching the
            dehydrator.  Measure the voltage at the terminal strip.
 
 Disconnect the power cord and check the position of the
            circuit breaker.
 
 
 If the circuit breaker is off, the cause of the overload may
       be shorted wiring, shorted motor windings, or a short in the
       pressure sensitive switch.<
 
 Dehydrator stops and starts repeatedly before reaching
       preset transmission line pressure:
 
 Check for large leaks in the transmission line or connecting
       line tubing.
 
 Check the connecting line tubing for restrictions such as
       kinks.  Reroute the tubing to remove kinks.
 
 Check to see if the transmission line is too restrictive for
       the pressure delivered by the dehydrator; that is, the dehydrator
       produces more pressure than the line can handle.  If the line is
       too restrictive, connect a pressure regulating tank between the
       dehydrator and the line.  The tank outlet pressure can then be
       adjusted to suit the transmission line.
 
 Dehydrator runs excessively - 30% to 50% more than normal:
 
 Check the dehydrator running time and frequency of operation.
       An antenna system incorporating an automatic dehydrator should be
       designed so that the dehydrator runs no more than 72 minutes and 
       no less than 10 minutes during a 24-hour period.  If the running
       time is longer or operation occurs more frequently, there is major
       leakage in the system.
 | Check for external or internal leakage.  Disconnect
        the connecting line tubing from the dehydrator outlet, block the 
        outlet with your finger, and run the dehydrator.  The dehydrator
        should shut off at the preset pressure of 8 psi within one minute.
        If it does, the leakage is either in the connecting line or        
        or transmission line.  If the dehydrator continues to run after
        one minute, there is internal leakage. 
 Check the dehydrator for internal leaks.  Cap the outlet, run
        the dehydrator, and apply a soap solution at all fittings and around
        components.  Check components such as the back pressure regulator
        valve, pressure sensitive switch, humidity indicator, and the 
        pressure gauge.  Bubbling indicates leakage.  Tighten leaky fittings
        and replace leaky components.  Then recheck operation with the outlet
        capped; it should shut off at 8 psi within one minute.
 
 Dehydrator either does not start at pressure of 3 psi or shut
        off at 8 psi:
 
 Readjust the limits of or replace the pressure sensitive switch.
 
 Replace the motor-compressor unit or rebuild the compressor
        using compressor repair kit 39878.
 
 Color of humidity indicator either pink, brown, or white:
 
 Measure the delivery air flow rate.  It should be at least
        10 to 12 cubic feet per hour.  A flow rate that is too low or too
        high indicates that the back pressure regulator valve needs readjustment
        or it is defective.  If this adjustment or replacement does not 
        affect the flow rate, the compressor should be repaired or replaced.
 
 Check solenoid valve cycle time.  Incorrect cycle timing is
        caused by a defective solenoid timing motor or solenoid switch.
 
 Run the dehydrator for 12 hours and check the humidity indicator.
        If there is little or no color change, replace the dryer assembly.
        (The dryer assembly includes the solenoid valves.)
 |